4–20 mA scaling, with the signal state visible.
Convert current, percent span, and engineering units while distinguishing calibrated range, overrange, and common diagnostic regions.
Analog instrumentation
Scale one signal three ways.
Enter current, percent span, or an engineering value. All three outputs update from the same configurable linear range.
12.000000 mA
50.000000 %
50 psi
Within the nominal 4–20 mA measurement span.
This scale uses common configurable limits: saturation at 3.8 and 20.5 mA, with failure alarms at ≤3.6 and ≥21.5 mA. NAMUR NE 43 provides the failure-signaling framework; confirm the transmitter and control-system configuration before diagnosing a fault.
This release does not apply square-root extraction, sensor characterization, damping, or temperature compensation. Reverse-acting ranges are supported by entering an LRV greater than the URV.
4 mA represents 0% span and 20 mA represents 100% span. Values outside that calibrated interval are extrapolated linearly; their diagnostic meaning depends on the instrument’s configured saturation and alarm behavior.
Primary standards and calculation sources